VRV Operation

This tech tip is written by experienced tech and VRF / VRV specialist Ryan Findley. Thanks, Ryan! (Note: Ryan refers to VRV rather than VRF because he specializes in Daikin, and these articles are written from a Daikin VRV perspective. Ryan has also written an article about VRV basics and some VRV installation tips.)


This tech tip will cover the different modes of operation of a VRV system, along with some of the unique control features of the VRV machines.

First, before we discuss how the machines accomplish the actual heating and cooling of the space, let’s define a few terms that we use frequently.  

Target Evap/Target Cond – VRV machines have target condensing temperatures and target evaporator temperatures that change based on load. It’s not uncommon to see some of these numbers get pretty far off what a standard A/C will run. The only reason to hook gauges to one of these machines is to verify the accuracy of the pressure transducers.

Four-Way Valve – Reversing valve. There are multiple four-way valves on these machines. VRV 3 has two (a heat exchanger four-way valve and the dual-pipe four-way valve), and VRV 4 has three (two heat exchangers, as outdoor coils are split coils, and one dual pipe).

Thermistor – A temperature sensing device that alters its resistance based on temperature. There are multiple different types of thermistors used across the product lines. Refer to your service manual or service app for temperature -> resistance charts.

A1P Board – The A1P board is the conductor of the machine. It talks to all the other boards; it is also the board where most of the thermistor inputs and solenoid coil outputs come from.

 

Before we discuss the individual modes of operation, I will cover how the bs boxes work to set the mode of operation for the fan coil.

With this diagram from the service manual, we can see how the refrigerant is routed through the bs box. The top is showing a unit in cooling mode and calling for cooling, the middle unit is in heating mode and calling for heating, while the bottom unit is in heating mode, but the thermostat is satisfied.

Now that we have a solid foundation, let’s get into the modes of operation.

Cooling Mode – There's no need to make this mode sound any more complicated than it is. The liquid line is always the liquid line, the dedicated suction line is active, and the dual gas line is also a suction line. EEVs in the indoor units are controlling to a target superheat at the outlet of the fan coil. This number is typically 9 degrees, but there are instances where that number can change. The further off setpoint, the target superheat will be lower. The opposite is true the closer you get to the setpoint. The outdoor unit(s) will leave the heat exchanger four-way valves, de-energize, and energize the dual gas four-way valve to use the dual gas line as an additional suction line.  Outdoor fans will modulate to maintain a steady discharge pressure. Here’s a visual aid from the VRV 3 service manual. This is taken from a heat recovery machine:

Parallel Operation– This mode of operation is used when both heating and cooling are needed. The liquid line and suction line remain dedicated to those tasks. So, the dual gas line will be a discharge line in this mode. It accomplishes this by leaving the dual gas pipe four-way valve de-energized. Outdoor heat exchanger control is determined by the load.  

Heating – During the heating operation, the system will energize the heat exchanger four-way valve and leave the dual pipe four-way valve de-energized. The dual gas line carries discharge gas to the bs boxes. The suction line is inactive in this mode. During this mode, the indoor EEVs control to subcooling control. Target subcooling in the indoor units is typically 9 degrees. The further off setpoint it gets, the lower the target subcooling goes. The opposite is true as it approaches the setpoint.

Defrost – Defrost is initiated based on demand. The machine is looking for three conditions that will cause a defrost:

  1. Small temperature drop across the outdoor heat exchanger
  2. If there is a temperature drop at the outlet of the heat exchanger
  3. If the low pressure stays low enough over a 2-hour period

Defrost will terminate if:

  1. The max defrost time is 5 minutes and 30 seconds, or 6 minutes have elapsed (depending on the model).
  2. Heat exchanger temp rises above 57.8 degrees for more than 90 consecutive seconds.
  3. Condenser pressure rises above 440.8 psi.

During defrost, the modules maintain whatever mode they were in when defrost was initiated. If this is a multi-chassis system, the units will alternate which one is in defrost to continue to provide heating. As each module finishes, the next one initiates. Fan coils continue to operate during this period. Fan coils in heating mode take their fan speeds to the lowest speed; if any fan coil happens to be in the off mode, the fans will turn off. EEVs move to 160 pulses or 224 pulses, depending on the model of the outdoor unit.

Oil Return – Oil return is used to bring oil back to the outdoor units. Since oil is an insulator along with a lubricant, oil return is necessary to maximize the efficiency of the indoor heat exchangers. Oil return is initiated if:

  1. Run time of 8 hours or 2 hours after a power cycle
  2. On-demand based on target evap, target condenser, and compressor speeds

Oil return terminates in cooling mode, either after 5 minutes or if the suction line temperature minus the target evaporator becomes less than 41 degrees.  

Oil return terminates in heating mode if evaporator pressure drops below 31.9 psi or 9 minutes.

Backup Operation – If a unit faults out on a compressor-related fault, the machine will go into automatic backup operation if the indoor units are turned off and then back on by the centralized controller. The unit will run with the offending compressor disabled for 24 hours, then try to run it again. To get out of backup operation, cycle power to the outdoor units.

Emergency Operation – This is used when there is a need to lock out a compressor until you can get back to it to replace it. In VRV 3, the entire module will be locked out. With VRV 4, you can lock out individual compressors or the entire module. Emergency operation can be found in mode 2->38, 39, and 40.

—Ryan

Comments

loading

To continue you need to agree to our terms.

The HVAC School site, podcast and tech tips
made possible by generous support from