Trap and Vent – A Drain Debacle

This picture is from a recent call I ran that clearly had an interesting past. It had a condensate pump to pump the water just a few feet up to a drain that went to a common drain. The “cleanout” after the trap is supposed to be a vent, not a cleanout, which means it needs to be uncapped and vented higher than the indoor drain pan so that if the drain backs up, the water goes back into the system and trips the condensate switch.  We could not raise the vent with the current position because it would come right up in front of the filter.

My best guess is that when the installing contractor installed a new, larger air handler, it no longer had the fall they needed to get the existing drain, so they capped the vent (seen in the photo above before it goes into the wall).

I'm using this system as an example because it has every possible drain “don't” you could come up with:

  • No cleanout
  • No float switch (condensate switch) to prevent pan overflow
  • Vent improperly placed or causing filter obstruction
  • Using a pump when one wasn't originally needed
  • Using a common drain with no vent
  • No insulation on the condensate drain horizontal runs

We rectified as much of it as we could, which included:

  • Adding a condensate switch
  • Repiping with a proper cleanout and vent before the pump
  • Insulating the horizontal portions

Unfortunately, we couldn't eliminate the pump, and I forgot to take “after” photos.

This is an example of a drain properly pitched, insulated, trapped, and vented with a system and secondary pan switch installed. Two things I do notice on this one is that the pan doesn't look like it overlaps 3″ at the top of the unit, The cleanout would be better right above the trap, and I can't tell what's supporting this drain to ensure the pitch stays correct.

It's amazing how much there is to the simple, humble condensate drain.

—Bryan

Related Tech Tips

What does "Saturated State" mean for Techs?
As we often do in these tech tips, we will start with the common and more practical explanation of saturation and then move to the more technical and nerdy explanation later. When we say “at saturation” or “saturated” in the HVAC/R trade, we are generally referring to the refrigerant that is in the process of […]
Read more
Conservation of Energy Law
“Electric Motor energy transformation” by coach_robbo is licensed under CC BY-NC-SA 2.0. Many scientists and philosophers contributed to the discovery of the law of conservation of energy. People have been aware of the concept of energy conservation since ancient Greece. These ancient Greek philosophers, such as Thales of Miletus, believed that all substances on Earth […]
Read more
The Good Old Heat Anticipator
As a technician, you most likely know some customers who still have an oldie thermostat (you know, those old mercury bulb things, like the round Honeywell CT87 and such). Keep in mind that those usually have an adjustable heat anticipator. If you’re newer in the field, you may not have seen or worked with those […]
Read more

4 responses to “Trap and Vent – A Drain Debacle”

  1. I never understood why FL does this. Up north we all just put a drain in the floor and drain it that way. Only one place in FL that I every went to drained it by going into the drain for the washer in the floor below.
    It’s got to be the most annoying and problematic way to do condensate drains. And if you do any places in Baldwin park those are the worst – running drains from the 2nd floor down, then out back behind the garage, which has got to be over 100ft of drain.

  2. Drains being a substantial amount of my calls during the A/C season in the northeast, I do have to say that sticking to the old 3/4″ solid PVC traps is a pain when rectorseal makes a cleanable drain trap that can be installed just as easy (yes and one that comes with a float switch). Other than cost, is there a particular reason why people still choose not to use these types?

    https://www.amazon.com/Rectorseal-83114-113B-Trap-Brush/dp/B00BMUFSGI/ref=sr_1_1?crid=2ZJ0OY9L2Y2V6&dchild=1&keywords=rectorseal+83114+2+ez+113b+trap+kit+with+brush&qid=1586054641&sprefix=rectorseal+113%2Caps%2C156&sr=8-1

  3. So basically the vent in condensate lines is to help the water go down the drain line?

  4. Yes. When AC Coil precedes the Air Handler/blower, you have “negative” pressure (causing vacuum preventing water from draining); a P-trap negates that pressure differential allowing water to drain properly. All fittings of EZ-Trap allows easy cleaning, venting, and quick visual if trap has debris (also has a brush to clean ANY direction of the drain line).

Leave a Reply

Your email address will not be published.

This site uses Akismet to reduce spam. Learn how your comment data is processed.

loading

To continue you need to agree to our terms.

The HVAC School site, podcast and daily tech tips
Made possible by Generous support from