In this short podcast episode, Bryan talks about the placement of the TXV sensing bulb. He also explains how it affects the opening force on the TXV.

The TXV sensing bulb (or sensor on an EEV) provides the opening force for the valve. The warmer the bulb gets, the more the valve opens; the colder the bulb gets, the more the valve closes. The TXV also has a closing force provided by the spring pressure and equalizer (usually the external equalizer).

So, if you have a bulb that has been poorly mounted or insulated, you tend to have more opening force than the design. Your suction line will generally be colder than the airstream around the evaporator coil. If the sensing bulb has poor contact with the suction line, it will likely read warmer temperatures than it should.

When the TXV opens more than it should, the valve loses control and could lead to flooded conditions. (If that liquid gets to the compressor, then you could get catastrophic damage.) Generally speaking, improper TXV bulb placement will result in low superheat and potential flooding. When you have a high superheat or a starved evaporator, the sensing bulb placement is rarely the actual problem.

When mounting a sensing bulb, the suction line should be clean. Get rid of all Armaflex residue and ensure that the bulb is also clean. In some cases, you may need to insulate the bulb. You must also ensure that you mount the sensing bulb securely near the evaporator outlet, and you can be a few inches downstream of the external equalizer. Another common suggestion is to place the bulb on top of the line if the line is smaller than 7/8″ (larger than 7/8″, you can mount the bulb at 4 o’clock or 5 o’clock on the line).

Learn more about Refrigeration Technologies HERE.

If you have an iPhone, subscribe to the podcast HERE, and if you have an Android phone, subscribe HERE.

Work through this with the trade.

Highlight a short passage, or bring a question about a specific moment into HVAC No Bull Forum.

Discuss this reference → Related forum discussions

Comments

Mastering Your Meter Advanced Functionality with Louise Kellar (UEi Test Instruments)
Premature Coil Failure in Ductless Mini-Splits & VRF Equipment – Short #303
Advanced Refrigerant Recovery: Best Practices for Diverse Systems and Environments
The A2L & Refrigerant Transition – Short #302
Invented For Techs, by Techs: Inside Refrigeration Technologies’ “The Lab”
The Ethics of IAQ – Testing vs. Remediation Conflicts – Short #301
Is 400 CFM per Ton Always Right? w/ Ty
The MERV 15 Filtration Physics – Short #300
Tips for Being On Call w/ Ty
The Florida “M-Word” – Legal Boundaries & Tech Communication – Short #299

Author:

The HVAC School site, podcast, and tech tips are
made possible by generous support from