Our good friend Trevor Matthews from Emerson Canada joins us to talk about compressors, mostly preventing compressor failure and troubleshooting issues.

Whenever we’re installing or servicing a compressor, we need to think about possible systemic issues right off the bat. The compressor is the heart of the system, but everything else in the system affects how the compressor runs. You’ll want to know which type of compressor you’re working with as well as the manufacturer. As always, you’ll want to check the superheat, subcooling, amps, TD across the condenser, and (especially) discharge line temperature.

The compression ratio is also a telling sign of the system and compressor’s health. You take the compression ratio by dividing the absolute suction pressure into the absolute discharge pressure. However, we must also consider the compressor’s application; by design, refrigeration compressors can deal with higher head pressures than A/C compressors.

Anytime a compressor fails, you’ll want to investigate why it failed. You can only see what happened inside a compressor if you cut it open and inspect it. During the inspection, look for signs of overheating and damaged components. Whether a burnout, flooded start, or thermal overload caused the failure, you will be able to see clues about the failure and can piece together the compressor’s story. Once we finish troubleshooting and diagnosing a compressor, we can focus on preventing future compressor failure. We’ll have a better idea of the operating conditions we need to avoid.

Trevor and Bryan also discuss:

  • Head pressure (discharge pressure vs. liquid line pressure)
  • Compressor types
  • Compressor overheating
  • Return gas temperature
  • Burnout
  • Line driers
  • The 80/20 rule
  • Flooded starts
  • Short cycling
  • Non-bleed TXVs
  • Recovery and evacuation
  • Thermal limit
  • Advanced temperature scroll protector (ATSP)

Emerson Flow Chart – https://www.hvacrschool.com/wp-content/uploads/2020/08/2004ECT-126_NOTRUNNING.pdf

Compressor Installation Guide –

https://hvacrschool.com/wp-content/uploads/2018/01/Compressor-Installation.pdf

Emerson System Cleanup Bulletin –

https://climate.emerson.com/CPID/GRAPHICS/Types/AEB/ae1105.pdf

Learn more about Refrigeration Technologies HERE.

If you have an iPhone, subscribe to the podcast HERE, and if you have an Android phone, subscribe HERE.

Work through this with the trade.

Highlight a short passage, or bring a question about a specific moment into HVAC No Bull Forum.

Discuss this reference → Related forum discussions

Comments

Advanced Refrigerant Recovery: Best Practices for Diverse Systems and Environments
The A2L & Refrigerant Transition – Short #302
Invented For Techs, by Techs: Inside Refrigeration Technologies’ “The Lab”
The Ethics of IAQ – Testing vs. Remediation Conflicts – Short #301
Is 400 CFM per Ton Always Right? w/ Ty
The MERV 15 Filtration Physics – Short #300
Tips for Being On Call w/ Ty
The Florida “M-Word” – Legal Boundaries & Tech Communication – Short #299
Becoming a GRIT Host or Mentor w/ Leilani
Behind the Drywall – The Psychrometrics of a Hidden Moisture Failure – Short #298

Author:

The HVAC School site, podcast, and tech tips are
made possible by generous support from