In this short podcast episode, Bryan explains how hydrostatic pressure can build up in refrigerant cylinders and present a hazard to technicians.

Your refrigerant cylinders have tare weight and water capacity values stamped on the tank. You’ll want to use these when weighing the refrigerant you recover because you don’t want to exceed 80% capacity. However, capacity changes when the liquid density changes; that density will change with pressure and temperature.

Hydrostatic pressure builds up when you have overfilled refrigerant vessels. When those vessels get warm, the density will decrease, and the liquid refrigerant expands. At some point, the vessel will contain 100% liquid and can no longer expand, so hydrostatic pressure will build. When that happens, you have a dangerous situation on your hands; the vessel may even explode.

AHRI recommends using 77 degrees as a guideline for figuring out the vessel capacity. However, we recommend using 130 degrees out of an abundance of caution; the back of your van probably won’t get much hotter than that, so we use it as an operational maximum.

We only get hydrostatic pressure when we recover refrigerant as a full liquid. When we recover refrigerants like R-410A in the liquid phase, we get a 45-PSI increase for each degree (Fahrenheit) of temperature increase. For R-22, that number is about 60 PSI; with R-134A, that number is about 40 PSI. When we get temperature swings from an ice bucket (~32 degrees) to the back of a hot van (~130 degrees), the pressure can build up within the vessel.

We also need to think about hydrostatic pressure when pumping down systems with microchannel coils. Hydrostatic pressure can build up in the receiver, and liquid can fill your condenser.

Learn more about Refrigeration Technologies HERE.

If you have an iPhone, subscribe to the podcast HERE, and if you have an Android phone, subscribe HERE.

Work through this with the trade.

Highlight a short passage, or bring a question about a specific moment into HVAC No Bull Forum.

Discuss this reference → Related forum discussions

Comments

Premature Coil Failure in Ductless Mini-Splits & VRF Equipment – Short #303
Advanced Refrigerant Recovery: Best Practices for Diverse Systems and Environments
The A2L & Refrigerant Transition – Short #302
Invented For Techs, by Techs: Inside Refrigeration Technologies’ “The Lab”
The Ethics of IAQ – Testing vs. Remediation Conflicts – Short #301
Is 400 CFM per Ton Always Right? w/ Ty
The MERV 15 Filtration Physics – Short #300
Tips for Being On Call w/ Ty
The Florida “M-Word” – Legal Boundaries & Tech Communication – Short #299
Becoming a GRIT Host or Mentor w/ Leilani

Author:

The HVAC School site, podcast, and tech tips are
made possible by generous support from