EPA Section 608 Changes Every Tech and Contractor Needs to Know (Podcast)

In this episode of the podcast, Jeremy Arling from the EPA comes on and answers some common questions about the new rule changes that affect recovery, leak repair, recordkeeping, and evacuation on HVAC and refrigeration systems.

EPA 608 rules regulate the actions that technicians must take when it comes to refrigerants and the atmosphere, such as venting, recovery, and evacuation. It has always been illegal to vent HFCs, including R-410A. The changes to EPA 608 attempt to treat all refrigerants equally; R-410A would be on equal footing with HCFC R-22, for example. EPA 608 also clarifies the actions that require certification, including the purchase of ozone-depleting substances.

It is not illegal to recharge CFC or HCFC refrigerants. However, the availability of HCFC refrigerants will dwindle over time; systems will need to be charged with reclaimed refrigerants, not new R-22.

EPA 608 will also crack down on recordkeeping for recovery and reclamation. The technician does NOT have to keep the records; it is the responsibility of the company. However, the technician should keep track of the recoveries they do and provide those records to their companies.

When recharging leaking systems with over 50 lbs of refrigerant, technicians should know that HCFC-reliant appliances must be repaired, retrofitted, or retired within specific timeframes. There is no minimum time frame between the leak repair and verification testing; however, the EPA recommends testing within 10 days of the repair.

The EPA has approved the use and recovery of flammable refrigerants for a handful of industrial applications. Most of these also receive exemptions from the venting prohibition.

Resources

You can find the complete rule update HERE. You can also find Jeremy's presentation slides HERE and a quick sheet for technicians HERE.

If you want an app to help you keep a record of recovered refrigerant, I would suggest looking at the R-Log app HERE.

If you have an iPhone, subscribe to the podcast HERE, and if you have an Android phone, subscribe HERE.

Comments

Michael Lee
Michael Lee @bryanorr

Clear and accurate explanation of section 608. Thx for bring this to real day to day technicians in the field..
Rules are not against hvac contractor or technicians. Just better practices in recovery and tracking disposal of refrigerants.
Thanks
Brian Orr
Jeremy Arling

5/17/17 at 10:57 AM

Clear and accurate explanation of section 608. Thx for bring this to real day to day technicians in the field..
Rules are not against hvac contractor or technicians. Just better practices in recovery and tracking disposal of refrigerants.
Thanks
Brian Orr
Jeremy Arling

Manuel Diaz
Manuel Diaz @bryanorr

Thanks for the update.just on time and on target.

5/23/17 at 04:14 PM

Thanks for the update.just on time and on target.