EER in the Field – Short #231

Make & share a podcast clip

Keep the exact passage and a link to the full episode. Choose up to three minutes, with enough context to be fair to the speaker.

Preview uses this episode’s audio. Browser audio export, when supported, takes the length of the selected clip. Nothing plays until you choose Preview.

In this short podcast episode, Bryan talks about EER (Energy Efficiency Ratio) and SEER (Seasonal Energy Efficiency Ratio) and how to calculate EER in the field.

EER and SEER are ratings that we often see on equipment (as are SEER2 and EER2) based on a ratio of an output to an input. Whereas coefficient of performance (COP) is a direct ratio of watts out to watts in, EER and SEER account for BTUs and watts. EER and SEER indicate the cooling capacity (in BTUs) we get from the watts we put in.

The ratio changes based on field conditions, and EER2 and SEER2 have more realistic test conditions than EER and SEER (the static pressure for systems rated below 65,000 BTUs per hour was 0.1″wc for EER and SEER, and it is now 0.5″wc for EER2 and SEER2, which is much closer to average field conditions).

To determine EER, you have to figure out BTU production and stack it against your wattage. You’ll need to know your delta enthalpy (delta H), multiply it by the CFM, and then multiply the product of those by 4.5 to get your BTU output. A calculator on apps like measureQuick can help you find out your delta H, but you’ll need a proper wet-bulb temperature before you can do that.

You can determine CFM with a TrueFlow grid or manufacturer’s blower charts. Finding watts can be a challenge with ECMs and inverter-driven systems; it’s not as simple as volts x amps, and you will need a meter that can measure power factor and take readings from the condenser fan, compressor, and blower motor. That wattage becomes the number you divide into BTUs to get the EER. SEER is averaged over a season, HSPF is for heating instead of cooling, and you can convert the BTUs to watts (by multiplying by 3.41) and determine the ratio of watts out to watts in.

 

Have a question that you want us to answer on the podcast? Submit your questions at https://www.speakpipe.com/hvacschool.

Purchase your tickets or learn more about the 6th Annual HVACR Training Symposium at https://www.hvacrschool.com/symposium.

Subscribe to our podcast on your iPhone or Android.

Subscribe to our YouTube channel.

Check out our handy calculators here or on the HVAC School Mobile App for Apple and Android

Work through this with the trade.

Highlight a short passage, or bring a question about a specific moment into HVAC No Bull Forum.

Discuss this reference → Related forum discussions

Comments

Mastering Your Meter Advanced Functionality with Louise Kellar (UEi Test Instruments)
Premature Coil Failure in Ductless Mini-Splits & VRF Equipment – Short #303
Advanced Refrigerant Recovery: Best Practices for Diverse Systems and Environments
The A2L & Refrigerant Transition – Short #302
Invented For Techs, by Techs: Inside Refrigeration Technologies’ “The Lab”
The Ethics of IAQ – Testing vs. Remediation Conflicts – Short #301
Is 400 CFM per Ton Always Right? w/ Ty
The MERV 15 Filtration Physics – Short #300
Tips for Being On Call w/ Ty
The Florida “M-Word” – Legal Boundaries & Tech Communication – Short #299

Author:

The HVAC School site, podcast, and tech tips are
made possible by generous support from