Compressor Overheating – Short #99

In this short podcast episode, Bryan explains what happens to a compressor when it's overheating. He also covers possible causes and troubleshooting strategies.

One of the Kalos techs came across an overheating compressor case that looked like a textbook TXV problem: the superheat was high at the condensing unit on the compressor side. However, the air handler superheat was appropriate, and the suction pressure was low. TXVs, however, respond to the superheat dropping and reduce the pressure even more. Overall, the mass flow rate and velocity drop, meaning that the refrigerant temperature can increase as it spends more time in the suction line.

We were missing a few key measurements to diagnosing compressor overheating. In those cases, we want to know the return gas temperature, discharge line temperature 6 inches out from the compressor, and the compression ratio (absolute discharge pressure / absolute suction pressure). You'll generally want to see a compression ratio between 2.6 and 3 on residential HVAC equipment; the lower the compression ratio, the better the efficiency. A compression ratio higher than 3 can lead to compressor overheating. A return gas temperature consistently above 65 degrees can also make a compressor run hot. The discharge line temperature should not exceed 225 degrees.

Then, you must determine if the charge is correct. (Are you starving the evaporator?) Check if you have restrictions and if your suction line is improperly insulated. Restrictions and heat transfer in the suction line can lead to compressor overheating.

It's bad for a compressor to run hot, but they can go their entire lives without tripping on the thermal limit. Compressors that run hot can have lubrication issues and will have shorter lifespans. The best thing you can do is try to reduce the compression ratio. (Clean the condenser, keep head pressure low, keep good indoor airflow, etc.)

Learn more about Refrigeration Technologies HERE.

If you have an iPhone, subscribe to the podcast HERE, and if you have an Android phone, subscribe HERE.

Comments

What We Learned From NCI Duct / Balancing Training
HVAC Systems for Architects: Making Sense of the Alphabet Soup – Short #273
Sizing Breakers and Conductors (for HVAC) – Have Things Changed?
Absorption Cooling – The Rise and Fall and Rise – Short #272
Combustion Analysis w/ Tony G.
Residential vs. Commercial HVAC Sales
When Ammonia Ruled the World – Short #270
Humidity, Airflow, and Refrigeration
The Finned-Tube Coil – Short #269
Are Two Are Better Than One: Understanding Tandem Compressors

Author:

loading

To continue you need to agree to our terms.

The HVAC School site, podcast and tech tips
made possible by generous support from