Modulation Motors

Modulation motors are not often seen in residential equipment, but we see them a lot in commercial and industrial applications on many different types of equipment. I see them primarily on larger burners to control the fuel firing rate, but they also control water flow through heating coils, the water level on cooling towers, and countless other applications. Anytime you need to control the flow of a medium (gas, water, air) and have valves or dampers that modulate flow, a mod motor probably has been used for it at some point. The more basic mod motors have been around for a long time, and in many applications, have been abandoned for newer and more precise control apparatuses, like servo motors. But there are still a ton of them in the field. I replaced three this week, as a matter of fact. So, I thought it fitting to share some information on them.

Here is your basic mod motor. As the label indicates, the voltage required to control the motor is 24 VAC. That is most common on mod motors I typically work on, but there are other control voltages utilized in different applications. For example, 2-10 VDC, 4-20ma, and other setups are fairly common. However, those get more complicated, and I want to keep this as simple as possible. So, we will focus on 24 VAC.

On the side of the motor, there is a square shaft end. That is the connection point by which the motor actually changes whatever it is controlling. The motor pictured above came off of a 350 horsepower Superior brand boiler with a Gordon-Piatt burner. The shaft end connects to a linkage arm; that linkage arm is connected to a gas butterfly valve and an air damper that controlled primary combustion air. As the motor stroked open, it opened the gas valve and air damper simultaneously, increasing the firing rate/size of the flame. As the motor strokes closed, the firing rate is decreased. This motor also contains high and low-end switches. The low fire end switch is normally closed (closed when the motor is in the minimum position), and the high fire switch is normally open, closing when the motor reaches the maximum open position. The end switches are used in industrial burners to prove that the valve is functioning to the burner controller. Generally, the motor moves to the fully open position during per purge/prelight off and then back down to the minimum open position during light off. If the motor does not open or close the proper end switch at the correct time, the burner control will not allow the sequence of light off to continue and go into a lockout. Not all mod motors contain high and low-end switches, but many do, and they do fail. I've replaced 5-7 over the last year.


The 24V style motors are often supplied with a transformer inside the motor housing, but that isn't always the case. As shown in the diagram above, the load side (24V/Common) wires to the T1 and T2 terminals on the motor. The other terminals typically used are R, W, and B. These terminals then connect to some variable resistance controllers. I am used to calling this type of controller a potentiometer, and I believe that is sufficient. As I am primarily a boiler guy, I will look at it from a boiler guy's perspective. The common potentiometer type modulation controls I see monitor steam pressure inside of the boiler. They contain the same terminals as the modulation motor (R, W, and B), and the terminal on the motor gets wired to the correlating terminal on the controller. The motor works off of a difference in resistance through the controller. Less resistance through the R and W terminals on the modulation controller causes the motor to drive to the minimum (closed) position. Less resistance through R and B causes the motor to drive to the maximum open position. As steam pressure rises and falls, the modulation controller changes in resistance through the three terminals. That is how the motor knows what position to be in while the burner is firing.

Troubleshooting a modulation motor is fairly simple. The control voltage is necessary for the motor to do anything. If control power is not present between terminals T1 and T2, then the transformer supplying the power should be checked. Transformers are checked by the voltage on the line side and the load side. The transformers supplied with the motors are 120 VAC line to 24VAC load. If the line voltage is not present, then we need to determine why. If 120V is present but no 24v on the load side, that would indicate a failed transformer. Transformers don't fail for no reason very often, so the control side of the circuit should be checked for shorts and grounds before the new transformer is installed, or you may run the risk of blowing the new transformer when the power is restored. Trust me, I speak from experience. If control power is present at T1 and T2, remove the wires from the R, W, and B terminals. A jumper from R to B should cause the motor to drive open, and a jumper between R and W should cause it to drive closed. Some motors contain a spring that causes the motor to close when power is removed, so keep that in mind when troubleshooting. If the motor doesn’t open or close when jumpered, and the correct control power is present, well, then you have yourself a bad motor. If the motor works properly when jumpered but not in normal operation when connected to the control circuit, then there is some issue with the components controlling the motor. Some of these systems can be quite complex, so good luck if you end up in this situation. You may need your thinking cap.

Any modulation motor you will encounter will operate the same. Control power is required, and some input to cause the resistance change needed for the motor to open or close. If you encounter issues with one, the basic motor troubleshooting techniques should be the same. It doesn't matter if it's on a boiler, cooling tower, water tempering system, or anything else.

 

—Justin Skinner

You can find more info on the Honeywell Modutrol line HERE.

 

Comments

Michae;
Michae; @bryanorr

Thanks
Great Article
Michael

12/25/17 at 09:59 PM

Thanks
Great Article
Michael

loading

To continue you need to agree to our terms.

The HVAC School site, podcast and tech tips
made possible by generous support from