Furnace Air Temperature Rise

Every gas furnace data plate/tag has a specification for the temperature rise through that furnace. It is shown in a range like 50-80° or 45-75°. Those first two numbers are the lowest recommended temperature rise; the highest allowed temperature rise through the furnace is usually a 30° difference. When possible, we want to get the rise toward the center of that range. So if our return air temperature is 70 degrees, the lowest supply air temperature we would want on the 090 furnace on the chart below is 95. The highest allowable supply air temperature for that unit would be 125, with the ideal being 110. We can attempt to do that through a combination of proper commissioning practices, primarily setting the airflow properly in heating mode.

Air temperature rise is the difference between the temperature of the return and the heated supply air from the furnace. Temperature rise must be measured during installation and must be within the range on the furnace rating plate. Air temperature rise is important not only for the longevity of the furnace but also for customer comfort.

So, what does temperature rise mean? How do we calculate it?

First of all, we need to verify that the furnace is firing on its full output (high fire) and that the manifold pressure is correct. Then, we need to let the appliance run for at least 15 to 20 minutes so that everything has a chance to acclimate. You then take the temperature of the return air into the furnace and then take the air temperature of the supply air leaving the furnace.

The supply air temperature should be taken several feet away from the furnace so that it isn't affected by radiant heat from the heat exchanger. You then subtract the return air temperature from the supply air temperature to get the air temperature rise through the furnace.

So, what can we learn from this number?

If you are too close to the low-end rating number with your rise, the air coming off the furnace will feel cool to the occupants. You may have complaints of “drafts” or not feeling warm.

If you are BELOW the low-end rise, you could even start to form condensation in the heat exchanger. That could shorten the heat exchanger's life due to corrosion. Low rise means you are moving too much air over the heat exchanger; this can (usually) be corrected by slowing the blower down.

It's more important that we mind the high end of the rated range. When we are near or over the high-end number, the furnace may begin cycling on the limit control. The limit is a safety control and is not designed to shut the furnace on and off regularly; it will eventually fail. Proximity to the high-end number is also a sign that you are overheating the furnace and will cause problems with the heat exchanger and other components.

When the rise is too high, you are not moving enough air over the heat exchanger. That can (and must) be corrected with a blower adjustment or by resolving the source of low airflow in the system, such as a dirty filter, blower wheel, etc.

As usual, when you see signs of low airflow, like high-temperature rise, look for the obvious maintenance-related issues first.

—Bryan

4 responses to “Furnace Air Temperature Rise”

  1. I’m a little confused by the statement following the example temperature rise ranges:
    “It is shown in a range like 50-80° or 45-75°. Those two numbers are the lowest recommended temperature rise; the highest allowed temperature rise through the furnace is usually a 30° difference.”

    Doesn’t the range indicate the lowest to highest recommended temperature rise, not just the lowest as stated? The difference in both examples is 30F which matches the typical difference (rise).

    • Hi Zig, you’re right that’s a typo and incorrect. We will get that fixed. . Let’s say for example you have 70 degree return air, the lowest correct supply air temp on a furnace with a 45-75 degree heat rise would be 115. The highest allowable would be 145. The ideal would be 130

  2. Bryan, what is the ideal solution when both the supply gas input and gas manifold pressures are within spec, the ECM blower is set to the lowest setting, and the temp rise is 3-5 degrees lower than the rated minimum for both low and high stages: slightly increase the orifice size? Thanks

    • Where are you putting your air temperature probes? I would try a few different registers or locations in the plenum to make sure your air temp readings are accurate. Then I would clock the gas meter to ensure proper input. Is that helpful?

Leave a Reply

Your email address will not be published. Required fields are marked *

This site uses Akismet to reduce spam. Learn how your comment data is processed.

Related Tech Tips

Infrared vs. Heated Diode Leak Detectors
Every HVAC/R tech needs an electronic leak detector nowadays, and with low-GWP HFC and HFO refrigerants getting more and more commonplace, every HVAC/R tech needs a VERY sensitive electronic leak detector. (Yes, electronic leak detection does work.) We often see three types, but let's toss out the corona discharge leak detector right off the top. […]
Read more
Venting for High-Efficiency Gas Furnaces - Part 2 Assembly
This article was written by senior furnace tech Benoît (Ben) Mongeau. Ben hails from the frozen tundra of Ontario, Canada, where high-efficiency gas furnaces are commonplace. While some codes and practices may be different from the US, I find that most of it is common sense and translates pretty well. One glaring difference between Canada […]
Read more
Calculating Target Delta T w/ Manufacturers' Data
This tip was a COMMENT on the sensible heat ratio tip left by Jim Bergmann. As usual, Jim makes a great point; once you get the “sensible” capacity for a piece of equipment at a set of conditions, you can easily calculate a true target delta T. Another interesting thing you can do is use […]
Read more
loading

To continue you need to agree to our terms.

The HVAC School site, podcast and daily tech tips
Made possible by Generous support from