Flex Ducts – Best Practices

Some techs and contractors swear that flex ducts are an evil invention and should never be used in ANY circumstance. I agree with what duct design expert Jack Rise said on the podcast when I asked him about flex ducts:

“There's a lot of problems with flex duct, there really is, and it's a good product, but we abuse it… It's a good product, it's just poorly handled.”

While the proper sealing of ductwork in unconditioned spaces is nearly universally recognized as important, a flex system rarely gets installed properly in these other important areas.

Fully Extend the Flex 

Some guidelines suggest pulling a 25′ piece of fully extended flex for one full minute before attempting to install it. That reduces the compression and the depth of the corrugation (the accordion spiral inside the duct). The more compressed the duct is when installed, the greater the air resistance of the duct will be. The air duct council states that 30% of compression can result in 4 TIMES the air resistance. That means that fully extending the flex is a big deal, and it may be one of the most overlooked aspects of flex system installations. Cutting off that 2-6′ of extra flex at the end instead of just “using the whole bag” can make the difference between a good and a poor duct system in many cases.

Strap and Support the Flex 

Jack Rise spoke about how he tested a duct and measured a 0.2″ wc change in static when he altered a duct from sagging to being properly strapped. In retrofit applications, many companies focus on “sealing” connections. However, they often don't truly address sagging ducts with proper strapping. The allowable amount of sag is only 1/2″ per 4′ of length, which isn't much. Don't ONLY rely on the code required strapping in your jurisdiction; just because a system passes inspection doesn't mean it's installed correctly.

Keep the Curves to a Minimum 

When designing a duct system, you must calculate TEL (total effective length), not just length. In a flex system, each curve has a HUGE impact on the TEL, and when a field install doesn't match the design, it can throw the whole system out of whack both from an air balance standpoint as well as a system performance by increasing the TESP (total external static pressure). Every bend and angle matters, so keep it extended, properly routed, and well supported, and all will be well so long as the design is correct.

Seal all the connections

As with all ducts, the connections need to be well sealed. With flex, this will generally need to be done with mastic, and the BEST way is to fully seal and allow the inner liner to dry before pulling the insulation over the connection. Also, keep in mind that leaks, where the boot/can meet the sealing, are very common leak points, and it's a good idea to seal them from the inside or outside to the final floor or ceiling before installing the grilles.

For more info, go to the ADC (Air Duct Council) website at flexibleduct.org or download their excellent guide HERE.

—Bryan

One response to “Flex Ducts – Best Practices”

  1. Note in the figure says 1/2” per foot, in the text it says 1/2” per 4’ of length. Which is it?

    I love your stuff and this site . . . As a maintenance guy, I just have trouble overlooking problems.

Leave a Reply

Your email address will not be published. Required fields are marked *

This site uses Akismet to reduce spam. Learn how your comment data is processed.

Related Tech Tips

Liquid Line Solenoid Valves: Long Line Applications
Pump down solenoid valves are commonplace for any refrigeration technician. They are energized with the compressor still running, shutting off flow in the liquid line so that the refrigerant is pumped into the condenser and receiver. The compressor will then shut off once a low-pressure switch opens the circuit when the pressure falls below a […]
Read more
Control Voltage Overamp - The Less Usual Cause
In many cases when a low-voltage or control circuit blows a fuse, it's because one of the circuits is shorted to ground or common. That may happen because of rubbed-out wires, shorted components or boards, etc. Routing wires sensibly and using proper grommets to avoid rubouts and shorts will help prevent those problems. Less commonly, […]
Read more
4-20ma Control Basics
Back in the “good old days,” controls were all analog and mechanical; that simply means they acted in a directly connected and variable manner based on a change in force. Both pneumatic (air pressure) and hydraulic (fluid pressure) systems are examples of mechanical or analog controls. When the pressure increases or decreases on a particular […]
Read more
loading

To continue you need to agree to our terms.

The HVAC School site, podcast and daily tech tips
Made possible by Generous support from