Electric Heat & Blower Interlock

In residential air handler/fan coils, it is common to use a high-voltage interlock between the blower and the electric heat strips to ensure that the blower comes on whenever the heat is on.

The problem is that it CANNOT work the other way around where the heat comes on with the blower.

Heat strips are generally going to draw 20+ amps, depending on the voltage and KW rating. You CANNOT power them through a typical relay like a blower relay or board, generally rated for 15 amps or less.

The way the interlock is wired is really quite obvious, but it's easy to forget because it's the reverse of what we are used to with a relay.

In short, we connect the blower to the “common” terminal on the relay, L1 power to the normally open (n.o.) terminal, and the load (out) side of the heat strip contactor /relay/sequencer to the normally closed (n.c.) terminal.

This diagram from Carrier shows the blower connected on the common terminal and constant power coming in on black to the normally open terminal from the right side of the transformer primary.

Let's use this 90-340 relay as an example. The blower would connect to 1, power to 3, and the heat strips to 2.

I made a video on it as well, if you need it. The result is that the blower runs with the heat, but the heat doesn't run with the blower.

—Bryan

Related Tech Tips

Why (and When) Do We Need Defrost?
Why Defrost? Let's start with the basics and move on from there. Defrost is necessary when the coil temperature drops below 32°F. Defrost can be as simple as turning the compressor off for a period of time or as elaborate as reversing the flow of refrigerant for the whole system or just parts of the […]
Read more
A Simple Piping Practice
Although there are various line lift, sizing, and trapping guidelines depending on oil and refrigerant type, there is one guideline we can all understand easily and remember to apply. This guideline is to slope suction lines towards condensing units/compressors. Keeping the suction line sloped toward the compressor, especially with long overhead lines, helps return the […]
Read more
What is Flux?
In HVAC, you will hear the word “flux” used in two totally different parts of the trade. Magnetic flux is the lines of force that emanate from a magnet, and you often hear about magnetic flux lines in discussions of motor theory. This type of flux has nothing to do with that… Flux in soldering, […]
Read more