Air Changes Confusion

Air changes per hour (ACH/ACPH) simply describes how many times the quantity of air in a room (or structure) is completely replaced per hour.

If you have a 10'x10'x10′ room, the room contains 1000 cubic feet of air. If the supply and return to the room is supplying a balanced 100 CFM (cubic feet per minute) of air to the room, you would have 100 CFM x 60 minutes = 6,000 CFH (cubic feet per hour), which would equal 6 air changes per hour (6,000/1000 = 6).

Different spaces have different ventilation requirements based on occupancy level (how many people are in the room) and use type. This is a fairly simple thing to calculate based on the cubic feet of air in a room. This is NOT the heat gain/loss of the space; it is only the ventilation rate of the space. Generally, ACH is used as a guideline or reference for design and not as a basis for the design; it's more of a solid rule of thumb used to check a ventilation design against the real world.

This ventilation rate shouldn't be confused with the outdoor air requirements, which is a different but related consideration and is based on ASHRAE 62.1 and 62.2.

In some cases, when discussing ventilation for an entire structure, ACH will be used to describe “tightness” and is referenced in many codes as a standard for the structure. For example, when performing a blower door test, a building test professional will use an air changes number to demonstrate whether a home or building is built to a tightness standard and how much supplemental outdoor air needs to be added to the space per hour.

Even more specifically, a standard called ACH50 is used with a blower door to calculate the leak rate of a structure when the space is pulled into negative 50 pascals of pressure by the blower door and the leak rate calculated.

In most cases, a room/zone will be sized for airflow according to the heat gain/loss to include outdoor air requirements. Then, the ventilation requirements will dictate the need for additional mechanical ventilation or fan-on position to provide the required air changes per hour.

In short, don't simply provide a room with system airflow that is consistent with the air change per hour rule of thumb and assume it will be properly conditioned and balanced. As with most things, it isn't that simple.

—Bryan

 

 

Leave a Reply

Your email address will not be published. Required fields are marked *

This site uses Akismet to reduce spam. Learn how your comment data is processed.

Related Tech Tips

The House is the Biggest Duct
This article was inspired by a podcast episode about the house being the most underappreciated duct with Joe Medosch. You can listen to that podcast HERE. We probably think about sheet metal, flex duct, or the ever-controversial duct board when we think about ducts. It’s probably shiny and out of sight in most homes. But […]
Read more
Diagnosing and Finding a Refrigerant Restriction
Photo by Ulises Palacios Refrigerant circuit restrictions can be common things like a plugged filter drier or a restricted metering device. They can also be more difficult to diagnose and stem from exotic issues like a kinked liquid line, blocked evaporator feeder tube, or a compressor connected improperly with a discharge line full of solder […]
Read more
3-Phase Motors—The Basics
Fundamentally, three-phase, alternating current motors are about as simple as a motor gets. The power company produces three phases by spinning magnets. Then, on the other end, we produce electromagnets that spin the motor according to the same 60 cycles per second frequency (60hz). All three phases are 120 degrees out of phase from one […]
Read more
loading

To continue you need to agree to our terms.

The HVAC School site, podcast and daily tech tips
Made possible by Generous support from