Why and how to adjust a TXV/TEV

As we discussed in an earlier podcast, a TXV is designed to maintain a specified and constant superheat at the evaporator coil outlet. It does this through a balance of forces between the bulb pressure (opening force), equalizer pressure (closing force), and spring pressure (closing force). Spring pressure can be adjusted on some valves, but why and when would you do that?

For the quick, cut-to-the-chase version, turning the adjustment on the bottom of an adjustable valve clockwise = higher superheat and counterclockwise = lower superheat. However, before you start messing with the adjustment, I suggest you read on.

First, the valve must be an adjustable type; many valves on small equipment are not adjustable and have no hex cap at the base.

Here are some other items you need to consider first:

Proper Subcool

Before an expansion valve can function properly and do its job, it must have a full line of properly subcooled liquid refrigerant all the way to the inlet. On a split system, checking the subcooling at the condensing unit is a good start, but you also need to make sure there isn't a significant temperature drop all the way up the expansion valve inlet. Keep in mind that some valves have a screen right at the valve inlet, so a restriction even at that point will cause operational issues.

Required Pressure Drop 

For an expansion valve to function, there needs to be a significant pressure differential between the evaporator's design pressure and the liquid pressure entering the expansion valve (in many cases, 100+ PSIG). During cooler times of the year, the outdoor condensing pressure/temperature may drop to the point that the required difference in pressure may not exist. In these cases, the valve may no longer be able to maintain the target superheat. While low ambient controls may be employed to rectify the issue in some cases, in many cases, you must simply be aware that the valve will not function as expected.

Improper Bulb Placement 

Ensure that the bulb is mounted on the suction line flat and tight with a proper strap. It is never a bad idea to insulate the bulb, and anytime it is exposed to ambient air, it is a necessity.

When to Consider Adjustment 

Now you are at the point where you can consider whether that valve could use some adjustment. First, measure the superheat right at the evaporator outlet in the same general location as the TXV bulb and equalizer. In most cases, the superheat at that point should be 5-10 degrees, but refer to the manufacturer's specs when in doubt. In some cases, you will not have a pressure port at the evaporator, so you must rely on a pressure reading outside. Use common sense when assessing the situation; realize that there may be some pressure drop on a 100′ line set, and there should be very little in a 10′ line set. Make some allowance according to the situation.

If the system runs VERY low or VERY high suction pressure or superheat readings that are way out of range, it is very unlikely that adjusting the valve will remedy it. Usually, valve adjustments are only for small superheat changes up or down.

The Forces at Play

The bulb pressure is the opening force of the valve, so when the bulb is warmer, it exerts more opening force resulting in a more “open” orifice. It exerts less opening force when it's cooler, resulting in a more “closed” orifice.

The equalizer is a closing force, so the higher the suction line pressure, the more the valve is forced closed. The lower the suction line pressure, the more the valve is forced open.

The spring is also a closing force. On an adjustable valve, increasing the spring tension/force results in lower flow and higher superheat, and decreasing the spring tension/force results in more flow and lower superheat. In short, counterclockwise = lower superheat, clockwise = higher superheat.

Making an Adjustment

Before you adjust anything, the system must have been running for a good long while, and you have observed that the superheat has stabilized. You then must check the entire system and surmise that everything else is functional—the valve is being provided with a fully liquid, properly subcooled, high enough pressure feed of refrigerant. If you find it is out of range at that point, then you can make adjustments.

  • CAREFULLY remove the hex cap from the base of the valve with a properly sized wrench and a backing wrench exposing the adjustment screw.
  • Turn 1/2 turn at a time clockwise (with a refrigeration wrench) to increase superheat or counter-clockwise to decrease superheat.
  • After a 1/2 turn adjustment, replace the panels and allow the system to run and stabilize.
  • Recheck the superheat and not the change.
  • Repeat as needed until the maximum setting is reached. NEVER force the adjustment screw too far; it should require minimal force to turn other than possibly initially to “unstick” the screw.

Adjusting a TXV/TEV is an advanced skill for a technician who has a good grasp on their readings and the forces at play. Tread carefully.

—Bryan

P.S. – Here is a great resource from Parker/Sporlan

Related Tech Tips

Air Velocity Quick Tips
Recommended Duct Velocities (FPM) Duct Type Residential Commercial / Institutional Industrial Main Ducts 700 – 900 1000 – 1300 1200 – 1800 Branch Ducts 500 – 700 600 – 900 800 – 1000   As service technicians, we are often expected to understand a bit about design to diagnose a problem fully. Duct velocity has many […]
Read more
Refrigerant Cycles Without Compressors
Many HVAC/R technicians (including me) describe the compressor as the heart of the refrigeration cycle. It prepares the refrigerant for the condensing process, which is crucial for heat rejection.  However, some refrigeration methods don’t require a compressor. In this article, we’ll look at those methods and their applications.   Gas movement without compressors As you […]
Read more
Workers of The World UNITE!
Yes, I'm walking a fine line with that title or even writing about Labor Day or workers' movements at all. So, let's take a step back, strip away the politics and economic theory, and talk about this from a human standpoint. Peter McGuire was born in New York in the 1850s to a poor family […]
Read more

One response to “Why and how to adjust a TXV/TEV”

  1. Thanks for the article. Very helpful.

    Is it true that the same TXV (e.g. an Emerson 0151R00177, 3.5 to 5 tons), when installed on a 3.5 ton system, versus a 5 ton system (everything else being the same), would have the adjustment screw backed out (on the 3.5 ton) from the neutral position (midpoint of screw travel), while the 5 ton system would be screwed in more?

Leave a Reply

Your email address will not be published.

This site uses Akismet to reduce spam. Learn how your comment data is processed.

loading

To continue you need to agree to our terms.

The HVAC School site, podcast and daily tech tips
Made possible by Generous support from