3-Wire and 4-Wire Condensing Fan Motor Connection

Diagram courtesy of Emerson

New techs have a common question of how to wire a condensing fan motor for 3 vs. 4 wires. Jesse Grandbois submitted this tech tip to help make it simple. Thanks, Jesse!


This tech tip is a quick one on the difference between wiring universal condenser fan motors and why brown + white is the same wire as white. This one seems to confuse even experienced technicians, but it's actually very simple once you see it. Now, keep in mind that wire colors ACTUALLY MEAN NOTHING, but the colors tend to be consistent on service replacement motors. As always, refer to the wiring diagram on the particular motor you are using.

I'll provide a diagram and explain the wires below.

Here's the 3-wire method:

  • White wire from the condenser fan motor to one side of power on the contactor (T1) and jumped to one side of the fan capacitor. This is AC power and not a dual capacitor, so the terminal side does not matter.
  • Black wire from the condenser fan motor to the other side of power on the contactor (T2).
  • Brown wire from the condenser fan motor to the other side of the capacitor opposite the jumper wire.
  • Cap off brown + white (unused).

Now, for your 4-wire method:

  • White wire from the condenser fan motor to one side of power on the contactor (T1).
  • Black wire from the condenser fan motor to the other side of power on the contactor (T2).
  • Brown wire from the condenser fan motor to the capacitor. Again, this is AC power and not a dual capacitor, so the terminal side does not matter.
  • Brown + white wire to the other side of the capacitor.

As you can see, the only difference is that there is no jumper from the contactor to the capacitor. That is because the brown + white and the white is the same wire. They're joined inside the motor. The brown wire with the white stripe is only there for convenience.

If you want to prove that the white and brown w/ white stripe are the same, take an ohmmeter and test between the two. You will find that it either reads zero or very low ohms, proving that they are directly connected within the motor.

 

—Jesse Grandbois

P.S. – If you would like to understand 3 or 4-wire connections within the entire process of replacing a condenser fan, please check out this article.

Related Tech Tips

Refrigeration Gas Defrost
Let's take a deeper dive into the magic that is gas defrost. Most techs who are familiar with heat pumps understand the basics of a gas defrost. When we apply this strategy to a larger system where we're only reversing a small part of the system, we need to add some controls and valves to […]
Read more
How to Make Better Decisions
That picture above is a WW2 poster reminding soldiers of informed self-interest, which is something we ought to consider when making decisions. We live in a world where we often make decisions quickly and expect to see quick results. That works whenever I buy from Amazon. I order a new belt, and it shows up […]
Read more
Changing Liquid Filter/Drier Cores Tip
This tip comes from market refrigeration and controls technician Kevin Compass. Thanks, Kevin! A little tip when changing liquid cores: If you start pumping them down, begin bypassing discharge gas into the shell to warm it up, push out the remaining liquid, and bring the shell above the dew point so that it doesn't sweat […]
Read more

8 responses to “3-Wire and 4-Wire Condensing Fan Motor Connection”

  1. Usually choose the 4 wire method and have always trained guys that way. Is there a difference in operation between methods? It’s always been my understanding that it doesn’t make a difference. I teach the four wire method because it is impossible to get confused.

      • Yes, my comment was for the 3 wire & what I was saying was instead of jumping from the starter/contactor you can also jump common direct from the cap.